Greenwich
St.
Building and
Mechanical
Inspection
EFTA00505930
Front of building showing brick pointing maintenance
needed.
::
--,,I,< -
IIIIIIIMIIII.MIMIIIIIIII.L,
v
:-:'
ii•EM. ,. .....
EFTA00505931
Exterior Brick — front façade of building
needs brick pointing maintenance
EFTA00505932
Newly
constructed
building adjacent
to 484
Greenwich — void
between
buildings needs
to be covered
from exterior
EFTA00505933
Fire and Water service — exterior covering
discolored, needs to be repainted.
EFTA00505934
Street hatch door — needs to be replaced at street
level to water tight hatch to avoid future basement
flooding
EFTA00505935
Main incoming electric from Con Edison still left open. Main electric supply
lines and box replaced. As you can see by the discoloration on the brick walls
and 100% saturated moisture readings on the brick that water sat in the
basement for a long period of time and destroyed the original electrical
service
EFTA00505936
New three phase service junction box installed, left
open by electrician, replaced after Hurricane Sandy
EFTA00505937
New electrical
equipment breaker
panel installed and left
open by electrician.
Check to see if the
owner had new panels
inspected by NYC
EFTA00505938
Rusted door in basement showing water level form
standing water from flood.
EFTA00505939
Basement ceiling — remove from water damage,
water entered street hatch above exit door and
destroyed ceiling
EFTA00505940
Masonry crack in
basement foundation
wall on Greenwich
street side, needs to
be checked by
structural engineer to
see how deep the
crack extends outward
EFTA00505941
Large Masonry crack in basement wall was previously
repaired with hydraulic cement, should be checked by
structural engineer
EFTA00505942
Main Stair well wall brick patching, possible
water seepage
EFTA00505943
Rusted stair steel shows water in basement for a long period of
time. Super storm Sandy hit October 29th, many basements on
Greenwich St. did not get pumped out until November 11th.
EFTA00505944
Basement at building next to 484
Greenwich pumped out on 11/08/12
EFTA00505945
New Trane XR80 boilers installed after hurricane Sandy,
air conditioning coil not hooked up to condenser unit
on roof. No air conditioning on the lower three floors
of the residence
EFTA00505946
Trane Heating /AC unit in basement
cooling coil for ac not connected to
condenser unit on roof no ac on
floors,1,2&3
EFTA00505947
Trane RX80 units picture shows no ac/coils hooked up
for Air Conditoning
EFTA00505948
New Gas Hot Water
Heater A/O
Smith
EFTA00505949
Gas & Fire
sprinkler
Service — looks
in good
condition
EFTA00505950
Elevator Control panel — looks newly installed,
elevator in process of being rebuilt. No elevator
service in house at this time
EFTA00505951
Hydraulic elevator not in operation — water in
hydraulic oil, this part of the elevator will possibly be
replaced or drained and repaired.
EFTA00505952
Main Water service and Fire service in
good condition
EFTA00505953
Fire Dry Pipe sprinkler system in good
condition.
,0
EFTA00505954
Fire dry pipe in good operating order
EFTA00505955
Lobby floor crack damage
EFTA00505956
Entrance lobby floor crack damage
EFTA00505957
Lobby floor Cracked in many areas
EFTA00505958
Lobby Floor cracks
EFTA00505959
Main steel support for warehouse
Industrial strength column and beam
EFTA00505960
Office floor Wood floor worn from
office chairs.
EFTA00505961
Front Door security intercom
operational /Central music system
EFTA00505962
Exposed air duct system
EFTA00505963
Windows operational but out dated
EFTA00505964
Side Window blocked by new building
and large masonry crack in wall
EFTA00505965
Wood floor damage laundry room, floor lifted
from water damage.
EFTA00505966
Kitchen appliances original to 1999
renovation
EFTA00505967
Terrace Blocked
by new building
wall
EFTA00505968
Brick in main
stair roof level
shows signs of
water seepage
EFTA00505969
Wood decking on roof - original needs
replacement due to rotting.
EFTA00505970
New Trane Condenser units installed above upper front
terrace above out door shower mechanical noise over head of
main roof terrace.
EFTA00505971
Bedroom AC unit also above roof terrace concealed
in wood enclosure.
EFTA00505972
Kitchen floor key pad area for ac/system alarm system
inter com central music system
EFTA00505973
Wood roof deck rotted wood and tripping hazzard.Deck
needs to be replaced.
EFTA00505974
Mechanical Equipment enclosure above roof deck check noise
level when all equipment is running .Access for maintenance
and installations limited.