Diesel Generators 10. 3200 Kw I Altematers 5.3500 Kra I Transfer Switches I Fuel Tanks I Trailers I Engine Parts I Alternator Part
SDMO I KOHLER I EROADCROWN I HIPCMER I JOHNDEERE I CUMMINS I PERKINS I MITSORSHI I VOLVO I STAMFORD I LEROY SOMER
GENERAL
POWER
GP J100UC3 Engine JOHN Alternator
DEERE, 4045HFS83, EPA/CARB Tier 3
LEROY SOMER, LSA44.3S5
100 KW JOHN DEERE GENERATOR
100 KW/125 KVA DIESEL GENERATOR SET. FULLY PACKAGED:
• JOHN DEERE Heavy duty diesel engine. 4 stroke. 1800rpm. Turbo. EPA
• LEROY SOMER brushless alternator. IP23 protection. Insulation class H
• SCHNEIDER. Main line circuit breaker. wired. maximum output rated
• EPA Tier 3 compliant engine per U.S. Environmental Protection Agency
• Digital auto-stan control panel. CE and UL compliant
• Incorporated metallic fuel tank for day use
• Auto Stan control feature included for interoperation with ATSIAMF
• 12V charging alternator and 12V DC electric starter motor
• 12V charged DC starting battery with electrolyte and cables
• Dry type air filter. fuel filter and oil filter elements installed
• Mechanically welded chassis with vibration isolators
• Each unit prototype and individually factory load bank tested
• The generator accepts 100% rated load in one step as per NFPA110
and meets 1508528.5 class G-3 for transient response
• Compliant with ISO3046. IS08528. BS4999. BS5514. BS500OPT99.
AS1359. IEC34. UTE5100. VDE0530 and IS09001:2000
AVAILABLE ACCESSORIES AND OPTIONS:
• Steel or Aluminum weather proof. sound attenuated enclosures
• UL142 listed. double wall fuel tanks from 50 to 10.000 Gal
• UL1008 listed, automatic transfer switches from 50 to 3000 Amp
MI compliant heavy duty road trailers from 3000 to 30000 Lbs
• Automatic battery chargers. Engine preheaters. Remote annunciators
and many more
Power ESP Power PRP
Voltage kWekVA kWe,kVA Standby Amps Dimensions - Open Weight - Open
480/277 100/ 125 91 / 114 150
460/265 100 / 125 91 / 114 157 Length : 1950mm (77inj 1187kg (2617lbs) Net
440/254 1001 125 91/114 164 Width : 1084mm 143in] 1440kgf3175lbs] Gross
240/139 100 / 125 91 / 114 301 Height : 1350mm [53inj
230/133 1001 125 91/114 314
220/127 100 / 125 91 / 114 328
208/120 1001 125 91 / 144 347
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications. in accordance with ISO
8528.1.
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-
1. Overload is not allowed.
TERM OF USE
Standard reference conditions ESP/PRP 25 C°/25 C° Air Intim Temp. 1000 m/1000 m m A.S.L. 60 % relative humidity.
WEATHER / SOUND PROOF ENCLOSURES
Model dB(A)@31t dB(A)@2311 Dimensions -Enclosed Weight - Enclosed Tank
Length : 2554mm 110 1in]
1597kg (35211bs]
Width : 1150mm [45in1 190 L
M129 78 68 Height : 1680mm 166in]
1850kg [4079lbsj
50 Gal
GENERAL POWER LIMITED, INC
1350 NW 78 Avenue! Miami, Flonda 33126
EFTA01097435
Diesel Generators 10.320CIKw I AltemMers 5.3500 Ka I TratINSwItche I Fuel Tanks I 'WINN I Engine Parts I AllemaINPAns
0 SDMO KOHtER I ERNIDCROWN I HIPCMER I !CNN DEERE I CUMMNS I PERIONS I MITSUBISHI I VOLVO I STAMFORD I LEROY SOMER
GENERAL
POWER
ENGINE SPECIFICATIONS
JOHN DEERE 4045HFS83,
Engine model 4-strokes, TURBOCHARGED, AIFVAIR, 4 Cylinders,
U.S. EPA / CARS TIER 3
Cylinders-arrangement 4-L
Displacement (C.I.) 4.48
Bore (mm) X Stroke (mm) 106 X 127
Compression ratio 19: 1
DATA Speed (RPM) 1800
Pistons speed (mis) 7.62
GENERAL DATA Maximum stand-by power at rated RPM (kW) 118
Frequency regulation (%) +145%
BMEP (bar) 15.9
Governor type ELECTRONIC
Exhaust gas temperature (°C) 580
EXHAUST SYSTEM Exhaust gas flow (Us) 380
Max. exhaust back pressure (mm CE) 750
Fuel consumption 110% load 31.1 Libr 18.2 gal/lx]
Fuel consumption 100% load 28.5 Uhr (7.6 gallhr)
FUEL SYSTEM Fuel consumption 75% load 24.8 Libr 16.6 gal/lx)
Fuel consumption 50% load 17.7 Libr (4.7 gatlhr)
Maximum fuel pump flow 74.7 Uht 119.7 gal/hr)
Oil capacity (L) 13
Min. oil pressure (bar) t.05
OIL Max. oil pressure (bar) 3
Oil consumption 100% load (L I) 0.08
Caner oil capacity (L) 12
THERMAL BALANCE Heal rejection to exhaust (kW) 111.15
Radiated heat to ambiant (kW) 14.39
Haat rejection to coolant (kW) 62.3+19.8
AIR INTAKE AIR INTAKE_entree_max% 375
Intake air flow (Us) 136
Emissions PM (g/kWh) 0.25
EMISSIONS Emission CO (g/kW.h) 1.47
Emissions HCNOx (g/kWh) 3.43
Emission HC (g/kW.h) 0.14
GENERAL POWER LIMITED, INC
1350 NW 78 Avenue! Miami, Florida 33126
EFTA01097436
Diesel Generators 10.3200 Kw I Alternators 5.3500 Kra I Transfer Switches I Fuel Tanks I Trailers I Engine Part. I AttematorPasts
SDMO r KOHLER I BROALCROYiN I HIPO'KER JOHN EEERE I CUMMINS I PERKINS I MIT9JISSHI I VOLVO I STAMFCR0 I LEROY S0VER
GENERAL.
POWER
ALTERNATOR SPECIFICATIONS
Alternator brand LEROY SOMER
Alternator LSA44.3S5
Number of phase 3
Power factor (Cos Phi) 0.8
Altitude (m) <1000
Overspeed (rpm) 2250
Number of pole 4
DATA Excitation system / Short Circuit reactance capability Auxiliary Excitation / 300% for 10 seconds
Insulation class / Temperature class H/H
GENERAL DATA Automatic Voltage Regulator Advanced. R438
Total harmonics TGH/THC <2
Wave form : NEMA=TIF-TGH/THC <50
Wave form : CEI=FHT•TGH/THC <2
Number of bearing
Coupling DIRECT
Voltage regulation 0 to 100% +/-0.5%
Recovery time (Delta U = 20% transitoire) (ms) 500
Continuous Nominal Rating 40°C (kVA) 131
Standby Rating 27°C (kVA) 144
Efficiencies 4/4 load (%) 91
Air flow (cfm) 0.44
Short circuit ratio (Koc) 0.33
Direct axis synchro reactance unsaturated (Xd) (%) 377
Quadra axis synchro reactance unsaturated (Xq) (%) 226
Open circuit time constant (Tdo) (ms) 2555
Direct axis transient reactance saturated a (%) 15
Short circuit transient time constant (ms) 100
(ID
OTHER Direct axis subtransient reactance saturated (X"d) (%) 9
Subtransient time constant (T"d) (ms) 10
DATA Ouadra axis subtransient reactance saturated (rq) (%) 10.8
Zero sequence reactance unsaturated (Xo) (%) 0.9
Negative sequence reactance saturated (X2) (%) 9.9
Armature time constant (Ta) (ms) 15
No load excitation current (io) (ms) 0.5
Full load excitation current (ic) (A) 2.1
Full load excitation voltage (uc) (A) 38
Recovery time (Delta U = 20% transitoire) (ms) 500
Motor start (Delta U = 20% perm. or 50% trans.) (ms) 238
Transient dip (4/4 charge) PF : 0.8 AR (%) 17.8
No load losses (kW) 2.72
Heat rejection (kW) 10.25
___LEROY® GENERAL POWER LIMITED, INC
1350 NW 78 Avenue! Miami, Florida 33126
EFTA01097437
Diesel Generators 10.3200 Kw I /diameters 6.3500 Kra I TransferSwitches I Puerile*, I Trailers I Engine Parts I AlternatorParts
SOHO I KOHLER I ERIKLYROWN I HiPasER I =OKVCEERE I CUNHAINS I HERONS I miT9JEKSHI I VOLVO I STAMFORD I LEROY SOMER
GENERAL
POWER
CONTROL PANELS
Standard NEXYS
NEXYS Specifications : Frequency meter. Ammeter. Voltmeter
• • •• • Alarms and faults : Oil pressure, water temperature,
Overcrank, Overspeed ( >60 kVA), Min/max alternator, Low
S fuel level. Emergency stop
Engine parameters : Hours counter, Engine speed, Battery
• e voltage, Fuel level, Alr preheating
Ostion TELYS2
Specifications : Frequency meter, Ammeter. Voltmeter
Alarms and faults : Oil pressure. water temperature. No start-
up. Overspeed. Min/max alternator. Minimax battery voltage.
Low fuel level, Emergency stop
Engine parameters : Hours counter, Oil pressure. Water
temperature, Engine speed. Battery voltage. Fuel level
Remote monitoring and control
ACCESSORIES AND OPTIONS
Option Automatic Transfer Switches, 110008 listed: 100 to 4000 AMPS
r
ASVCi With a Series 300 transfer switch, you get a product backed by
ASCO Power Technologies, the industry leader
EMERSON •True double-throw operation: single solenoid design is inherently
interlocked & prevents contacts from stopping between sources
•Easy-to-read flush-mounted control and display panel provides
LED indicators for switch position and source availability
U •Standard engine exerciser for weekly automatic testing with or
without load
•UL 1008 listed for Transfer Equipment and CSA C22.2 listed
•NFPA 110 for Emergency & Standby Power & the National
Electrical (NEC) Articles 700. 701 and 702
O• ion Fuel Tanks, IlL142 listed: 50 to 5000 GAL
•UL listed. Secondary containment tank meeting UL 142 tank
requirements
•NFPA compliant. Designed to comply with the installation
standards of NEPA 30 and NFPA 37
LISTED •Emergency pressure relief vents. Meets UL requirements: ensures
adequate venting of inner and outer tank under extreme pressure
and/or emergency conditions
•Electrical stub-up area with removable end channel
•Normal vent • Inner tank emergency vent sized to UL 142 specs
•Direct reading mechanical fuel gauge • Fuel in basin switch
•Satin black paint finish
GENERAL POWER LIMITED, INC
EFTA01097438
Diesel GiNineff 10.7200 Kw I Allem/don 6.7600 KY. I Tranvia Switches I Fuel TSOM I fl an I EOM Put I MOM&Put
S0MO I KOHLER I ERNID0ROWN I HIPOAFR I JOHN DEERE I CUMMINS I PERMS I 1.1ITSUESSHI I VOLVO I STAMECRD I LEROY SOWER
GENERAL
POWER
Weatherproof / Super Silent
M129 Enclosure
STANDARD FEATURES
▪ 12 gauge electro-zinc powder coated steel for maximum corrosion resistance (Phosphatizing degreasing. Non-chromic
passivanon, Osmosis purified rinsing and High durability polyester resin thermosetting powder paint)
■ 29dB(A) Internal-mounted critical silencer and flexible exhaust connector offering maximum component life and
operator safety
■ Fade-. scratch-, and corrosion-resistant. Automotive-grade textured finish resulting in advanced corrosion and
abrasion protection as well as enhanced edge coverage and color retention
■ Up to 51mm (2in) Acoustic insulation with hydrocarbon sealing film that meets FMVSS 302 flammability classification
and repels moisture absorption
■ Interchangeable modular panel construction. Allows complete serviceability or replacement without compromising
enclosure design
■ Service access. Multi-personnel doors for easy access to generator set controller. breaker and service points
■ Externally mounted emergency stop button, Single point lifting hook and Tamper proof "securit" viewing control window
■ Cooling air discharge. Weather protective design featuring a vertical air discharge outlet grille. Redirects cooling air up
and above enclosure to reduce ambient noise
■ Cooling/combustion air intake with a horizontal air inlet. Sized for maximum cooling airflow
■ Heavy duty Polyamide plastic hinges. Dichromate galvanized bolting and Stainless steel rivets for lifetime longevity
■ Meets and exceeds NFX41002 Salt spray test. NFT30049 UV Performance test, NFT30038 Paint adhesion test and
2000/14EC Low sound directives
I C 0
C.
E
I •
POW ER
•
foI an
www.genpowerusa.com
Sound level
Model Dimensions Weight Tank
dB(A)@31t dB(A)@23ft LW A (in) (Ibs) (Gal)
GP 1000C3 78 68 N/A 101 x 45 x 66 3521 50
GENERAL POWER LIMITED, INC
1350 NW 78 Avenue / Miami, Florida 33126
EFTA01097439
Entities
0 total entities mentioned
No entities found in this document
Document Metadata
- Document ID
- 3d218aff-57b5-4583-becd-c0aa3f75cf83
- Storage Key
- dataset_9/EFTA01097435.pdf
- Content Hash
- bdd3fdfdccc890e02939042254fdd097
- Created
- Feb 3, 2026