EFTA00592474.pdf
dataset_9 pdf 133.2 KB • Feb 3, 2026 • 3 pages
ALANIL SCHWARTZPE CONSULTINGENGINEERS
353 W. 481" STREET
NEW YORK, NY 10096
Richard Kahn
HBRK Associates Inc.
575 Lexington Avenue, 4th Floor,
New York, New York 10022
July 26, 2013 Re: 9 East 71st Street
New York, NY
Engineering Report
Dear Mr. Kahn,
The following is based on our investigation of the conditions in the 3"
floor bedroom in the above space. The purpose of the investigation is
to attempt to remedy any adverse comfort conditions the space. The
investigation consisted of a review of the existing design drawings for
the building, the modification of the bedroom system previously
completed, and an inspection of the cellar and 6" floor mechanical
rooms as well as a non-destructive inspection of the bedroom and
surrounding area.
1) Based on the existing drawings the return air in the sitting room
and bedroom totals 1670 cfm. The air originally supplied to those
two rooms totaled 2735 cfm. With the addition of the 10 ton air
handler, the supply air into the bedroom had increased by an
additional 1000 cfm, resulting in a total difference of over 2000
cfm. The original return was designed as a "plenum return;" the
return duct collects air above the ceiling, requiring the air to
migrate to the space above the ceiling thru architectural slots
above the bedroom crown molding.
We recommend:
a) increasing the quantity of return air to the space by installing
a booster fan in the return ductwork to match the increased air flow
generated by the supply air handler. The booster fan should be
installed as far away from the bedroom as possible (potentially near
the service stair) to minimize any sound generated from the fan.
b) Reroute the ductwork in the corridor to allow the return air to
be collected below the ceiling, but above the crown molding.
c) The above recommendations for duct modification are based on
review of the existing DESIGN drawings and visual inspection of all
conditions below the ceiling. The as built conditions above the
sheetrock ceiling could not be determined; the design may need to be
modified once the actual conditions are determined.
2) The 10 ton air handler is a pre-manufactured unit that was designed
to provide a design temperature in the bedroom of 60 degrees F. At
that temperature, the dehumidification capacity of the unit is
limited. The amount of humidity that can be removed from the space
is inversely proportional to the supply temperature coming off of
the cooling coil; the lower the supply temperature, the more
humidity can be removed from the room. This unit can only produce a
EFTA00592474
• Page2 July26,2013
temperature of approximately 55 degrees. While this is adequate for
cooling, this cannot bring the RH in the space below 70% when the
room temperature is 60 degrees.
We recommend:
a) obtaining a custom built unit which has a chilled water coil
that can produce a discharge temperature of approximately 48
degrees F. This temperature can bring the humidity in the
space down to 50% or lower, which is within the comfort range.
With air temperature this low, it is likely that the space
would be overcooled. A hot water heating coil should be added
to the unit AFTER the cooling coil. This would raise the
temperature of the supply air, without affecting the
dehumidifying capacity of the unit, and enable us to regulate
the temperature of the bedroom. There will be some additional
piping modifications to the piping system required by this
installation. Depending on the unit selected, the chilled
water requirement may be increased. The pump that presently
feeds chilled water to the air handler may be inadequate and
need to be replaced as well.
3) We were informed of another potential option discussed being the
installation of a Mitsubishi split system in the closed adjacent to
the bedroom.
We have reviewed this at this time do not recommend this for the
following reasons:
a) The minimum published indoor operating temperature for the
Mitsubishi unit is 59 Degrees F. This is very close to our
standard room temperature of 60 Degrees. As with the chilled
water units, the lower the space temperature, the more
difficult it is to dehumidify. While there is no data from
Mitsubishi concerning this reduction, a similar system(Daikin)
has the moisture removal capacity reduced to 1/3 of its
nominal total when the space temperature is lowered from 70
degrees to 61 degrees(lowest published data point). We are not
confident that this type of system will significantly reduce
the moisture in the room.
b) The proposed location of the indoor unit is close to the
bedroom. Although the Mitsubishi fan coils are very quiet,
they still generate some sound. With the unit that close to
the bedroom, there will not be an adequate length of ductwork
installed to achieve significant sound attenuation.
c) the Mitsubishi unit will be subject to maintenance on a
regular basis. The original design concept of the residence
was to have all mechanical equipment remote from the living
area, either on the 6th floor or the cellar.
d) The split system concept requires piping run from the 3" floor
closet up to the roof. This will result in substantial general
conditions construction (carpentry, painting, etc) over and
above the mechanical work. The work for the chilled water
design all be completed in the mechanical spaces; the return
duct revisions will require some duct modification in a few
local areas.
EFTA00592475
• Page3 July26,2013
Let me know if you have any questions or comments
Very truly yours,
Alan R. Schwartz PE
EFTA00592476
Entities
0 total entities mentioned
No entities found in this document
Document Metadata
- Document ID
- 33e82b30-3502-42b9-b378-3e79165d38da
- Storage Key
- dataset_9/EFTA00592474.pdf
- Content Hash
- adb43e682110536d1f58b889ca82619a
- Created
- Feb 3, 2026