May 28, 2014
From: Duane Zachman
To: Brice Gordon
Subj: Whole House Protection from Electrical "Brownouts" and "Spikes"
Brice,
This is to summarize the information and budgets we have researched to find a solution to the problem that is
occurring at the main house with electrical faults. These faults arc "Brownouts" and "Spikes" from the electric
utility provider and cause equipment and electronics to be damaged. Since the problem is from the utility, we
have explored options that protect the entire house electrical. Because the electrical service for the house is
large and single phase, it makes equipment difficult to find availability and price. The following are 3 options
we obtained information on.
Option 1 - Two Voltage conditioners 240 volt, 200 KVA Estimated Price $103,000.00
Voltage Conditioners 2 x $28,000.00 = $56,000.00
Freight $ 2,000.00
Engineering $ 5,000.00
Wire, Conduit, Crane $10,000.00
Labor Installation $30,000.00
Option 2 — Two Voltage Regulators 240 Volt, 200 KVA Estimated Price $117,000.00
Voltage Regulators 2 x 35,000.00 = $70,000.00
Freight $ 2,000.00
Engineering $ 5,000.00
Wire, Conduit, Crane $10,000.00
Labor Installation $30,000.00
Option 5 - Two UPS 240 Volt, 200 KVA Estimated Price $450,000.00
UPS 2 x 200,000.00 = $400,000.00
Freight $ 2,000.00
Engineering $ 5,000.00
Wire, Conduit, Crane $10,000.00
Labor Installation $33,000.00
from a local
Please note that these prices arc budget numbers and not a fixed quote. Pricing was obtained
equipment. I hope this information is helpful. I am also attaching a brochure
supplier in the research of this
and a simple riser diagram to help explain this information.
Thank You
Duane Zachman
EFTA00600675
"CO SWF.'
r e's.•••rer"
Modular Power
AoPrr
Conditioning s or
System
The Toughest
Power Conditioner
on theMarket Today
.1fr"
The Staco Energy Products Company Automatic Advantages:
Voltage Regulator is based on a series regulation
Modular construction for easy customization
transformer controlled by variable transformers (Ws).
It offers tight output regulation, robust design and Options offer more features and functionality
easy customization. Extremely high overload/inrush rating
In today's world, the cost of electrical power and its Very low cost of ownership due to efficiency and
quality have become major operating concerns.The virtually maintenance-free operation
continuing increase in the cost of electrical power Trouble-free operation with no active devices in power path
has heightened interest in energy savings, and poor
1% or better output voltage regulation
power quality has been identified as a cause of
expensive malfunctions and shutdowns in new high Continuous voltage regulation—not crude step regulation
technology equipment.
Redundant manual regulation control
Voltage regulation problems account for more than (raise/lower switch)
90% of the power problems seen at most sites. The Individual coil protection—avoid catastrophic cascade failures
Staco Energy's base Automatic Voltage Regulator
Gold plated contacts on all coils
(AVR) provides protection against all but the most
extreme voltage swings. When additional non-voltage Nickel plated copper bus bar
issues occur, Staco Energy offers a series of options Easy, front panel access for service/installation
that address such issues as high voltage transients,
high harmonic content and site load balance. This No waveform distortion—no harmonics added
integrated and targeted approach provides site- Small footprint
specific power correction in a one-box solution.
Able to withstand the continuous vibration
of mobile applications
Warranty
The industry leading three-year warranty is our guarantee
that Staco Energyoffers the toughest, most robust Voltage
Regulation System on the market today.
atE?
EFTA00600676
Automatic Voltage Regulator
The Staco Energy Automatic Voltage Regulator's unique construction blends precise regulation,
high availability, and ruggedness into a highly customizable package.
Base Regulator System
Motorized Variable Transformer controlled, series regulation transformer
Technology
(buck-boost transformer with secondary wired In series with the load)
kVA rating (single-phase) 2.5, 5, 7.5, 10, 15, 25. 37.5 (up to 500 kVA, contact factory)
Voltage (single-phase) 120, 208, 230, 240, 277, 380, 400, 480
9, 15, 30, 45, 75, 112.5, 150, 225, 300, 400, 500 (up to 1,000 WA.,
WA rating (three-phase)
contact factory.)
Voltage (three-phase) 120, 208, 240, 380, 400, 420, 440, 480
Input Regulation (±1% output) +10% / -20%
Input Regulation
+10%1-25%
(+1% -5% output)
Response Time < 2 cycles
29 V/sec. at 480 Vac 3 phase, 48 V/sec. 240 Vac single phase.
Correction Time
Contact factory for other times.
Efficiency Typical 97% for PLC units and 99% for AVR units
Mean Time Between Failure Greater than 200,000 hours
Harmonic Distortion None added
Harmonic Content None added
Overload Rating 33% - 2 hours 50%-1 hour 100% -15 minutes 1,000% - 30 cycles
Output impedance Less than 1% (maintains tight regulation with 100% load step)
Load Power Factor (pf) 0 lagging to 0 leading
Attitude (operating) 10,000 feet without derating
Temperature (operating) 0° to 40° C
Heat Dissipation Voltage Regulator Typical 38 BTU/Fir/kVA; Power Conditioner Typical 95 BTU/Hr/kVA
Audible Noise Less than 45 dBA
Wiring Hardwired
Enclosure NEMA 1 100% front accessible standard with NEMA 3R and others upon request.
Power Conditioning Options
Base Un' , P al r Optional 1
Power Problem Voltage . isolation Surge Advanced Individual
" nsformer Protection MP Controller Phase Control
Brownout X
Under Volta / Sat X
Over Volta / Su X
H' h Volta,e Transient X
••htnin Protection X
Unbalanced Load X
3rd Harmonic Reduction X
Line Noise X
Establish a Neutral on 0 •ut X
Front Panel LCD Di a X
Remote Communications & X
Control
• ut Re•utation *1% 5%) t1%(5%) t1%(5%) *0.5 Vac *0.5 Vac
e rACO
NfRGY
EFTA00600677
Applications for
Voltage Regulation Surge Protection
General use surge suppressor designed for small service entrance panels or
• BROADCAST: Regulation for broadcast individual equipment protection. Provides against high voltage transients
transmitter sites and studios. generated both internally (such as motors, environmental control equipment,
• COMMERCIAL High-rise building manufacturing, and office equipment) and externally (substation switching
whole floor regulation or power transient, system faults, and severe weather such as lightning strikes).
conditioning, input voltage regulation ■ 25 year free replacement warranty on surge protector
for elevator control, large A/C chillers, ■ Parallel configuration provides 40kA (40,000 amps) per phase
lighting, and other sensitive non-critical peak surge current protection
systems. • Response time <= I nanosecond
■ INDUSTRIAL: Industrial automation, ■ Protection: all modes: L-N, L-L, N-G, L-G
process control, CNC, factory robotics, ■ ANSV1EEE C62.41/62.45 Categories C, B and A with susceptibility up to medium
facility level of point-of-use, heavy load exposure levels. Designed to protect against externally generated impulse
machinery regulation. transients and internally generated switching/ring wave transients.
■ UL 1449 latest edition, CUL. UL 1283 listed
• MARINE: Dockside or shipboard voltage
regulation and power conditioning. Advanced Communications & Control (MP Controller)
■ MEDICAL: Medical Imaging: X-ray, ■ Increases output regulation to ± 0.5 Vac from standard ±1%
CAT Scan, and MRI power conditioning; ■ LCD display with numeric/special function keypad
building or whole floor regulation. ■ Monitor and manage output voltage and set points
• MOBILE: Commercial broadcast and ■ Three form tecontact closures and eight logic level output signals
military mobile communication trucks, IP Multiple set points may be programmed for variable speed, ramping, and
trailers and shelters. dwell for dynamic voltage control
■ User programmed to accept peak-to-peak, average or RMS measurements
Points to Consider ✓ Optional RS232 and RS422 communications for remote monitoring and control
for Sizing and Configuration ■ MP controller standard on three-phase systems with Individual
Phase Controlled (IPC)
OUTPUT:
Individual Phase Control
Voltage? Vac
Phase? Single Three Provides * 0.5 Vac regulation (w/MP Controller) on each phase, independently.
Neutral Available? Yes No Provides load balancing for applications with unbalanced, single-phase loads
or unbalanced and fluctuating utility power.
Frequency? 50 Hz 60 Hz
Double Shielded Isolation Transformer (Wye-Wye)
• INPUT: ■ Provides extra protection & isolation between the utility and the load
• Noise attenuation
Voltage? No
120 dB common mode
Neutral Required? Yes No
■ 60 dB transverse mode
kVA Required No
ci All copper construction
— Traps 34 harmonic and triple harmonics
Surge Suppression? Yes No a Removes electrical ground noise/interference
Individual Phase Control? Yes No ■ Creates a bonded neutral (newly derived source)
Advanced MP Controller? Yes No ■ 97% or greater efficiency
Isolation Transformer? Yes No • Required where input & output voltages differ
External Bypass? Yes No Additional Options
Other? Yes No ■ Electrically and mechanically isolated external maintenance bypass
in a free-standing or wall-mount cabinet
■ Input and output circuit breakers
■ Additional / custom power meters
Custom enclosures for harsh /outdoor environments
EFTA00600678
Circuit Diagrams
Three Phase, Single Line Control Three Phase, Individual Line Control
r v./SILL
111,1I•TCPWA
POCULATOI
rsayscamo
About Staco Energy Products
Since 1937, customers worldwide have been In addition to the Automatic Voltage
Regulator we offer a wide array of
relying on Stoco Energy Products Company power quality products, including:
to deliver voltage control andpower quality • Unintemiptible Power Supplies
solutions tailored to their needs. • Power Conditioners
As a leading power quality resource, we offer • VoltageRegulators
our customers world-doss support; from our • Power Factor Correction and
thorough applications assessment, to our HarmonkMitigation
ability to design and deliver a solution that is • Activeliamionk filters
tailored to the specific needs ofour customers; • Variable Transformers
through delivery and commissioning. • CustomEngineered TestSets
Our professional, factory trained service
team is in place to ensure that our
customers'revenues are protected
and their investment provides them
with many years of trouble free operation.
Sroco develops totalpower solutions
for OEM and end user applications.
Represented locally by:
TACO Contact Us:
US Toll Free: 866-261-1 igt
Phone: 937-253-1191
CO ® E-mail: sales@stacoenetgy.com
PA"
EFTA00600679
Entities
0 total entities mentioned
No entities found in this document
Document Metadata
- Document ID
- 21781809-45ea-4a99-8a5a-ec63c55306b7
- Storage Key
- dataset_9/EFTA00600675.pdf
- Content Hash
- ae0f29ad5b75a1a3566919c9cb2c3ef7
- Created
- Feb 3, 2026